Voltage Drop Calculator
About This Tool
This calculator helps electricians, engineers, and homeowners determine whether a wire size is adequate for a given circuit, or find the smallest wire that meets both ampacity and voltage drop requirements. It supports three international standards: NEC (US), IEC 60364 (EU), and BS 7671 (UK).
How to Use
- Select your standard (NEC, IEC, or BS 7671) and choose between voltage drop calculation or wire size recommendation
- Enter your circuit parameters: voltage, current, wire length, conductor type, and insulation
- Review the results showing voltage drop percentage, pass/fail status, and recommended wire size
Methodology
For NEC calculations, voltage drop uses the K-factor formula: VD = (K × I × L × 2) / CM for single-phase, where K is the resistivity constant (12.9 for copper, 21.2 for aluminum in ohms·cmil/ft), I is current in amps, L is one-way length in feet, and CM is the wire area in circular mils. For three-phase, the factor of 2 is replaced by 1.732. For IEC and BS 7671 calculations, the mV/A/m method is used with tabulated impedance values from the relevant standard tables. Ampacity is determined from NEC Table 310.16 (60/75/90 degree columns) or equivalent IEC/BS tables, then adjusted for ambient temperature and conduit fill derating factors.
Understanding Your Results
A green "Pass" result means the voltage drop is within the code limit for the selected circuit type. A red "Exceeds Limit" result means you need a larger wire size, shorter run, or lower current to comply with the standard. In Wire Size mode, the tool shows two recommendations: the minimum wire by ampacity (can safely carry the current) and the minimum wire by voltage drop (stays within the code limit). The larger of the two is the recommended size, and the controlling factor tells you which requirement drove the selection.
Sources
Practical Examples
Example 1: A 20A, 120V single-phase branch circuit using #10 AWG copper THHN, 100 ft one-way. Voltage drop = (12.9 × 20 × 100 × 2) / 10380 = 4.96V, which is 4.13% — exceeds the 3% NEC limit. Solution: upsize to #8 AWG (16510 CM), giving 3.12V drop (2.6%) — passes. Example 2: A 50A, 240V single-phase feeder using #6 AWG copper, 75 ft. Voltage drop = (12.9 × 50 × 75 × 2) / 26240 = 3.69V, or 1.54% — well within the 5% feeder limit.
Practical Tips
For long cable runs, voltage drop often requires a larger wire than ampacity alone. Always check both. A wire that passes ampacity but fails voltage drop will still cause problems at the load. Higher system voltage reduces percentage voltage drop proportionally. A 240V circuit has half the voltage drop percentage of a 120V circuit with the same wire, current, and distance. Parallel conductors can solve voltage drop problems on very long runs where a single large wire would be impractical or too stiff to install. Two sets of smaller wire can be easier to pull and bend. Always account for derating when wires share a conduit or run through hot spaces. The base ampacity from the table assumes a 30 degree Celsius ambient and no more than 3 current-carrying conductors.
All calculations are performed locally in your browser. No data is sent to any server.